Follow us :

Vacuum Interrupter HCJ5 1.14kv 125A for vacuum contactor

Vacuum Interrupter HCJ5 1.14kv 125A  for vacuum contactor
Vacuum Interrupter HCJ5 1.14kv 125A  for vacuum contactorVacuum Interrupter HCJ5 1.14kv 125A  for vacuum contactorVacuum Interrupter HCJ5 1.14kv 125A  for vacuum contactorVacuum Interrupter HCJ5 1.14kv 125A  for vacuum contactorVacuum Interrupter HCJ5 1.14kv 125A  for vacuum contactor
FOB Price

US $11.001 - 1800 piece

group name
Vacuum Interrupter
Min Order
1 piece
brand name
JUCRO
model
JUC505
Nearest port for product export
Ningbo, Shanghai, Others
Delivery clauses under the trade mode
FOB, CFR, CIF, EXW, DDP, DDU, Express Delivery
Acceptable payment methods
T/T, L/C, D/P D/A, MoneyGram, Westem Union, Cash, Escrow
update time
Wed, 18 May 2022 14:22:52 GMT

Packging & Delivery

  • Min Order1 piece

Briefing

Vacuum Interrupter
Rated voltage: 1.14kV
Rated current: 125A
Model: JUC505
Brand: JUCRO Electric

Detailed

HCJ5 1.14kv 125A vacuum interrupter for vacuum contactor

Vacuum Interrupters accept customized order according to technical drawing or samples.
Detailed Image

1. Brief introduction

The interrupter adoption porcelain and ceramics makes to insulate the outer shell. Contact is WCCu metal alloy material advanced technique of adoption Including bulk small. Breaking the abiliting strong the life span is long, maintenanle is simple, no explosion dangerous, no contaminate and the noise is low. It is extensive to used for coal mine , chemical engineering, Petroleum metallurgy etc. department, more than keeping with at the multifarious operation with the bad place usage of environment

  

2. Vacuum Tube main technique parameter

Rated voltage: 1.14 kv

Rated current: 125A

Rated making current: 1250A

Rated breaking current: 1000A

Limiting breaking current: 1250A

Rated short-time withstand current: 1000A

Rated short-time withstand voltage: 10 kv

Mechanical life: 1000000 times

Breaking operations AC3: 150000 times

Breaking operations AC4: 6000 times

Automatic closing force of the contacts: 25±10 N

Force required to hold contacts open at full stork: 40±10 N

Circuit resistance at lowest rated contacts force: ≤120μΩ

Limiting abrasion of contacts: 2 mm

Storage life: 20 years

Internal gas pressure: ≤1.33×10-3 Pa

No.

Parameter name

Unit

Value

1

Rated voltage

kV

1.14

2

Rated current

A

125

3

Rated frequency

Hz

50

4

Rated making current

A

1250

5

Rated breaking current

A

1000

6

Limiting breaking current

A

1250

7

Rated short-time withstand current

A

1000

8

Rated short-time withstand voltage

kV

10

9

Mechanical life

times

1000000

10

Breaking operations

AC3

times

150000

AC4

6000

11

Automatic closing force of the contacts

N

25±10

12

Force required to hold contacts open at full stork

N

40±10

13

Circuit resistance at lowest rated contacts force

μΩ

≤120

14

Limiting abrasion of contacts

mm

2

15

Storage life

year

20

16

Internal gas pressure

Pa

≤1.33×10-3

 Packing & Delivery 

Strong package, Safety first.

Inside with foam to support the product, put it in carton or wooden box, fixed it on pallet.

As long as possible to keep the products safe until it arriving customer's warehouse.

Clearly marking label outside of package, customers will be easy to identify their goods.
Our Company
20000 M2 of JUCRO Electric company land
1500 M2 of office building
5000 M2 of workshop building
Inside of JUCRO Electric office building
Inside of JUCRO Electric office building
JUCRO Electric office work area
Workshop

Vacuum Interrupter Workshop

Accept customized order.
Design the Vacuum Interrupter for you.

VCB Production Line

VCB Vacuum Circuit Breaker production Line.

VCB Production Line

VCB Vacuum Circuit Breaker production line, Engineers routine inspection.
Quality Inspection
 Carefully inspection of each product, Quality guaranteed 
 completely data records of entire process , all the product data can be traced.