Search This Supplers Products:High voltage electrical productsVACUUM INTERRUPTERVACUUM CONTACTORVACUUM CIRCUIT BREAKERVCB SWITCHGEAR PANELSUBSTATION
Packging & Delivery
Min Order1 piece
Briefing
Detailed
FZN25A-12(D)/T630 indoor AC high voltage vacuum load switch (hereinafter referred to as load switch) is suitable for three-phase AC, 50Hz, 12KV power supply network, as the breaking load current and closing short-circuit current. The product is equipped with manual and motor operating mechanism, especially suitable for occasions under severe conditions, without long maintenance period and frequent operation requirements. Vacuum load switch with fuses - fuse combination appliances (hereinafter referred to as combination appliances). FZN25A-12(D)/T200 can break short-circuit current for short-circuit protection. The product has a mechanism tripping, and the fuse has a bumper. When an overload current or a short-circuit current is passed, the fuse is blown, and the striker hits the trip device to automatically open the load switch to avoid phase loss operation.
Normal use environment:
1. Ambient air temperature: up to +40 ° C, minimum -25 ° C;
2. The altitude does not exceed 1000mm;
3. The daily average relative humidity is not more than 95%, and the monthly average is not more than 90%;
4. Earthquake intensity: below level 8;
5. The surrounding air should be free from harmful gases such as corrosive or flammable gases and water vapor.
Main technical parameter
Main electrical technical parameters
Item | Unit | FZN25A-12D/T630 | FZRN25A-12D/T200 | |
Rated voltage | KV | 12 | 12 | |
Rated Frequency | Hz | 50 | 50 | |
Rated Current | A | 630 | 200 | |
| Active load breaking current | A | 630 |
|
Closed loop current | A | 630 |
| |
No-load transformer | KA | 1600 | 1600 | |
Cable charging current | A | 10 |
| |
Rated transfer current | A |
| 3150 | |
Rated short-time withstand current (4S) | KA | 20 |
| |
Rated peak withstand current | 50 |
| ||
Rated short-circuit breaking current | KA |
| 3.15 | |
Rated short circuit closing current | KA | 50 |
| |
Rated short-time 1 min power frequency withstand voltage | KV | 42/48 | 42/48 | |
Rated lightning impluse withstand voltage(peak) | KV | 75/85 | 75/85 |
Main mechanical property parameters
Parameters | Unit | Numerical value | Remark |
Vacuum interrupter opening distance | mm | 6 |
|
Vacuum interrupter contact stroke | mm | -2 |
|
Isolation fracture opening | mm | ≥130 |
|
Interphase center distance | mm | 210±1 |
|
Three-phase closing of vacuum interrupter | ms | ≤3 |
|
Vacuum interrupter allows | ms | ≤3 |
|
Vacuum interrupter average closing speed | m/s | 0.6±0.2 |
|
Vacuum interrupter average closing speed | m/s | 0.9±0.2 |
|
Conductive loop resistance | μΩ | ≤300 |
|
Maximum operating torque required | Nm | ≤160 |
|
Mechanical life | Times | 10000 |
Motor technical parameters
Rated voltage | Rated output power | Normal operating voltage range |
220 | 70W | 85%-100% Rated voltage |
Shunt release parameter
Rated voltage | Normal operating voltage range |
DC220 DC110 | 80%-120% Rated voltage |
Outline technical parameter