COMMON CHARACTERSTICS
|
||||
Rated voltages
|
||||
Insulation voltage (V)
|
Ui
|
800 | ||
Impulse withstand voltage (kV)
|
Uimp
|
AC 50/60 Hz
|
8 | |
Operational voltage (V) | Ue | 690 | ||
Suitability for isolation | YES | |||
A | ||||
Pollution degree | IEC 60664-1 | 3 |
COMMON CHARACTERSTICS
|
|||
Control
|
|||
Manual
|
With toggle
|
■ |
|
With direct or extended rotary handle | ■ | ||
Electrical
|
With remote control
|
■
|
|
Versions | |||
Fixed | ■ | ||
Withdrawable | Plug-in base | ■ | |
Chassis | ■ |
CIRCUIT BREAKER | JCNSX250 | |||||||||
Breaking capacity levels
|
F
|
N
|
H | S | L | |||||
Electrical characteristics as per IEC/EN 60947-2
|
||||||||||
Rated curent
|
In | 40℃ | 250 |
|||||||
Number of poles | 2,3,4 | |||||||||
Breaking capacity(kA rms) | ||||||||||
Icu | AC 50/60 HZ | 220/240V | 85 | 90 | 100 | 120 | 150 | |||
380/415V | 36 | 50 | 70 | 100 | 150 | |||||
440V | 35 | 50 | 65 | 90 | 130 | |||||
500V | 25 | 36 | 50 | 65 | 70 | |||||
525V | 22 | 35 | 35 | 40 | 50 | |||||
660/690V | 8 | 10 | 10 | 15 | 20 | |||||
Service Breaking capacity(kA rms) | ||||||||||
Ics | %Icu | <500V | 100% | |||||||
Durablyity (C-O cycles) | Mechnical | 20000 | ||||||||
Electric | 415V | In | 10000 | |||||||
440V | In/2 | 20000 | ||||||||
In | 10000 | |||||||||
690V | In/2 | 10000 | ||||||||
In | 5000 | |||||||||
Characteristics as per Nema AB1 | ||||||||||
Breaking capacity (kA mrs) | AC 50/60 HZ | 240V | 85 | 90 | 100 | 120 | 150 | |||
480V | 35 | 50 | 65 | 90 | 130 | |||||
600V | 20 | 20 | 35 | 40 | 50 | |||||
Characteristics as per UL 508 | ||||||||||
Breaking capacity (kA mrs) | AC 50/60 HZ | 240V | 85 | 85 | 85 | - | - | |||
480V | 35 | 50 | 65 | - | - | |||||
600V | 15 | 15 | 15 | - | - | |||||
Protection and measurements | ||||||||||
short-circuit protection | Magnetic only | ■ | ||||||||
Overload/short-circuit protection | Thermal magnetic | ■ | ||||||||
Electrical | with netral protection(Off-0.5-1-OSN) | ■ | ||||||||
with ground-fault protection | ■ | |||||||||
with zone selective interlocking(ZSI) | ■ | |||||||||
Display/I,U,F,P,E, THE measurement/interrupted-current measurement | ■ | |||||||||
options | power meter display on door | ■ | ||||||||
operating assistance | ■ | |||||||||
counters | ■ | |||||||||
histories and alarms | ■ | |||||||||
metering com | ■ | |||||||||
device status/control com | ■ | |||||||||
earth-leakage protection | By Vigi add-on | ■ | ||||||||
By VIgirex relay | ■ | |||||||||
Installation/connections | ||||||||||
Dimensions(mm) and weights | ||||||||||
dimensions mm | fixed, front connections | 2/3P | 105*161*86 | |||||||
4P | 140*161*86 | |||||||||
Weight kg | fixed, front connections | 2/3P | 2.4 | |||||||
4P | 2.8 | |||||||||
Connections | ||||||||||
Connection terminals | Pitch | With/without spreaders | 35/45mm | |||||||
Large Cu or AI cables | Cross-section | mm² | 300 |